3.5

Connecting an external braking resistor

Connecting an external braking resistor
Damage to braking resistor - Risk of fire!
You must implement fire prevention measures for the external braking resistor (e.g. fire
protection housing, temperature fuse). The resistance of the externally connectable braking
resistor must be 3 ohms ± 10%.
The figure below shows the connection of an external braking resistor to interface X5051
(and X4060):
xL+
2DIx
Figure 3-5
PDC1000(F)
Equipment Manual, 02/2020, A5E48775040-AA
WARNING
Basic insulation
Supply voltage
Digital input
Connection of external braking resistor (example)
3.5 Connecting an external braking resistor
4R+, 4R-
Connection for external braking resistor
R
External braking resistor
Connecting
27