Continuing Operation

This section explains functions for continuing or automatically restarting Inverter operation using speed
search even if an error occurs.

Restarting Automatically After Power Is Restored

Even if a temporary power loss occurs, you can restart the Inverter automatically after power is restored to
continue motor operation. To restart the Inverter after power has been restored, set L2-01 to 1.
If L2-01 is set to 1, when power is restored within the time set in L2-02, the Inverter will restart. If the time set
in L2-02 is exceeded, alarm IUV (main circuit undervoltage) will be detected.
Related Constants
Name
Constant
Number
Display
Momentary power loss
detection
L2-01
PwrL Selection
Momentary power loss
ridethru time
L2-02
PwrL Ridethru t
Min. baseblock time
L2-03
PwrL Baseblock t
Voltage recovery time
L2-04
PwrL V/F Ramp t
* The factory setting depends on the Inverter capacity.
Setting
Description
Range
0: Disabled [main circuit
undervoltage (IUV)
detection]
1: Enabled [Restarted when
the power returns within the
time for L2-02. When L2-
0 or 1
02 is exceeded, main circuit
undervoltage (IUV) is
detected.]
A backup of the control power
supply is necessary for tempo-
rary power loss protection.
Ridethrough time, when
Momentary Power Loss Selec-
0.0 to
tion (L2-01) is set to 1, in units
of seconds.
Sets the Inverter's minimum
baseblock time in units of one
second, when the Inverter is
restarted after power loss ride-
through.
Sets the time to approximately
0.1 to
0.7 times the motor secondary
circuit time constant.
When an overcurrent or over-
voltage occurs when starting a
speed search or DC injection
braking, increase the set values.
Sets the time required to return
the Inverter output voltage to
normal voltage at the comple-
tion of a speed search, in units
0.0 to
of one second.
Sets the time required to
recover from 0 V to the maxi-
mum voltage.
Change
Factory
during
Open-
Setting
Operation
loop
Vector
0
No
A
2.0 s
No
A
10.0
2.0 s
No
A
5.0
*
1.5 s
No
A
10.0
*

Continuing Operation

Control
Methods
MEMOBUS
Register
Flux
Vector
A
4F0H
A
4F1H
A
4F2H
A
4F3H
35