4.9 How to Use Transfer Output

F Transfer output
type
F Transfer output
scaling
Parameters
• When using transfer output, add on the communications unit
(E53 CKF).
• You can select the following four data items in the transfer output type"
parameter (option mode) as the transfer outputs:
Present SP (default), Process value, Manipulated variable (heat),
Manipulated variable (cool).
• If the output assignment is changed when either the manipulated vari
able (heat)" or manipulated variable (cool)" parameter is selected, the
factory setting set point" is returned to.
• These transfer outputs can be scaled according to the settings of the
transfer output upper limit" and transfer output lower limit" param
eters before output. Setting of an upper limit value smaller than the low
er limit value is allowed, so reverse scaling can also be carried out. Also,
the scale can be enlarged by the upper and lower limit width specified
for each data item. The following example shows scaling of the heating
side manipulated variable.
Transfer output
(mA)
Reverse scaling
20
4
Transfer output
Transfer
upper limit: 0
output lower
limit: 100
Symbol
Transfer output type
Transfer output upper limit : Option
Transfer output lower limit

4.9 How to Use Transfer Output

Transfer output
(mA)
20
4
Manipu-
0
lated
Transfer
variable
output lower
(%)
limit: 10
Parameter Name: Mode
: Option
: Option
Enlarged scale
Manipulated
variable (%)
100
Transfer
output upper
limit: 80
Description
Transfer output designation
Transfer output scaling
Transfer output scaling
4–21