CHAPTER 4 APPLIED OPERATION
JStarting the
program run
F PV start
F Standby
operation
JEnd condition
Parameters
4–16
• When the program is configured by the time setup method, a ramp
priority PV start" can be selected as one of the run start conditions. If
you select PV start" in the PV start" parameter (expansion mode),
program operation is started from the position of the SP that first
matches the PV when program run is started. If the SP does not match
the PV , the program run is started from the beginning.
SP
Step 0
Disabled time
PV
• After the run instruction, the controller is reset until the standby time
elapses.
• Set the standby time in the standby time" parameter (level 2 mode)
within the range 0.00 to 99.59 (hours:minutes). Defaults is 0.00".
• After end of operation, the controller normally is reset. However, control
can be continued on the SP of the final step by setting the end condi
tion" parameter (expansion mode). If the end condition" is set, the SP
of the final step and [
• When the number of steps" parameter is changed after operation has
ended, the controller state does not change state. However, if control
with respect to the SP is continued, the SP switches to the new value of
the final step.
Note: The end of operation does not refer to the end of the pattern. It refers to
the end of executing the pattern the specified number of times.
Symbol
Parameter Name: Mode
Operation at power ON : Expansion
PV start
Standby time

End condition

Step 1
Step 2
Start point
] appears alternately on the No.2 display.
Operation when power is
turned ON
: Expansion
Start of program run
: Level 2
Start of program run
: Expansion
Operation end program run
Step 3
Time
Description