Transfer output type
Transfer output upper limit
Transfer output lower limit
• These parameters set the transfer output conditions.
• The transfer output type" parameter selects one of the following data items as the
transfer output type, and assigns this to transfer output:
Function
Present SP , Process value, Manipulated variable (heat), Manipulated variable (cool)
(during heating and cooling control)
• The transfer output upper limit" and transfer output lower limit" parameters are
used for scaling of transfer output. The setting range varies according to this output
data. Also, a lower limit value larger than the upper limit value may be set.
• During temperature input, the decimal point position of the set point or process value
is dependent on the currently selected sensor, and during analog input on the results
of scaling.
• Set the scaling of the present SP or process value within the sensor input indication
range.
"
Setting
"
"
"
• Default : [
F Related description
4.9 How to Use Transfer Output (page 4 21)
See
F Option units
E53 CKF
Model
Transfer Output Type
" Present SP
" Process Value
" Manipulated variable (heat)
" Manipulated variable (cool)
].
Option Mode
Conditions of Use
The transfer output function must be in
use.
Transfer Output Lower Limit to
Transfer Output Upper Limit
-1999 to 9999
-1999 to 9999
-5.0% to 105.0% (standard control), 0.0 to 105.0% (heating
and cooling control)
0.0 to 105.0%
5–47