Omron e5ck User Manual page 112

Digital controller (programmable type)
Hide thumbs Also See for e5ck:
Table of Contents

Advertisement

CHAPTER 5 PARAMETERS
Setup Mode
Alarm 1 type
Alarm 2 type
Alarm 3 type
• Alarm 1 to 3 type" parameters specify the operation of the alarm by the one of the
set values in the following table. For details of operation at an alarm, see page 3 10.
Function
Set Value
Setting
Default is 2 : upper limit".
F Related description
3.4 Setting Alarm Type (page 3 10)
F Related parameters
See
Alarm value 1" Alarm value 2" Alarm value 3" (Program mode)
Alarm 1 hysteresis" Alarm 2 hysteresis" Alarm 3 hysteresis" (level 2 mode)
Alarm 1 open in alarm" Alarm 2 open in alarm" Alarm 3 open in alarm" Control
output 1 assignment" Control output 2 assignment" Auxiliary output 1 assign
ment" (setup mode)
5–34
Settings
1
Upper- and lower-limit alarm
2
Upper-limit alarm
3
Lower-limit alarm
4
Upper- and lower-limit range
alarm
5
Upper- and lower-limit alarm with
standby sequence
6
Upper-limit alarm with standby
sequence
Conditions of Use
Alarms must be assigned as outputs. For
example, if alarm output 1 and 2 only are
assigned as outputs, the "alarm 3 type"
parameter cannot be used.
Set Value
Settings
7
Lower-limit alarm with standby sequence
8
Absolute-value upper-limit alarm
9
Absolute-value lower-limit alarm
10
Absolute-value upper-limit alarm with
standby sequence
11
Absolute-value lower-limit alarm with
standby sequence