6.4 Commands and Responses

JReading/writing parameters
F Reading parameters
Command
Response
F Writing parameters
Command
Response
This section describes commands and response in detail. The conventions
used in this section and data restrictions are as follows:
• Data is expressed in 1 byte units and in ASCII code.
• When the read or write data is a numerical value, the data to be set must
conform to the following conditions:
(1) The decimal point ." is not indicated in fractions.
(2) The leftmost bit of minus numerical data must be expressed as fol
lows:
A: 1, F: (minus)
[example]
10.0=[0100], 150.0=[A500], 15=[F015]
2B
2B
Unit
Parameter
No.
No.
@
1
2B
2B
Unit
Parameter
No.
No.
@
1
2B
2B
Unit
Parameter
No.
No.
@
2
2B
2B
Unit
Parameter
No.
No.
@
2
Parameters of a specified controller are read or written.
• Writing is possible only during remote operation.
• Reading is impossible during execution of auto tuning.
• The following are set aside as special commands. For details, see page
6 10.
• AT execute/cancel", Hold/Hold cancel" and Advance"
• For details on parameters in each setting level, see the tables on page 6 8
and 6 9.

6.4 Commands and Responses

4B
2B
FCS
0
0
0
0
2B
4B
End
Read data
code
4B
2B
FCS
Write data
2B
4B
End
Write data
code
2B
*
CR
2B
2B
FCS
*
CR
2B
*
CR
2B
2B
FCS
*
CR
6–7