CHAPTER 4 APPLIED OPERATION
F Multi-SP
J Transfer output
Parameters
4--8
The set points set to the "set point 0" and "set point 1" parameters (level
1 mode) can be switched for use. However, note that these parameters
cannot be set when the multi-SP function is not selected.
The set point can be switched up to 100,000 times.
When event input is "OFF", set point 0 is used, and when "ON" set point
1 is used.
When you have changed the set point, the set point of the currently
selected parameter is changed.
When you have switched between "set point 0" and "set point 1", the SP
ramp function works if the SP ramp function is enabled. The following
examples shows how the set point changes when you switch from set
point 0 and set point 1.
set point 1
set point 0

Event input

When using transfer output, add on the communications unit (E53-CKF).
You can select the following data items in the "transfer output type"
parameter (option mode) as the transfer outputs:
Set point
Set poing during SP ramp
Process value
Manipulated variable (heat), and
Manipulated variable (cool).
These transfer outputs can be scaled according to the settings of the
"transfer output upper limit" and "transfer output lower limit" param-
eters before output. Setting of an upper limit value smaller than the
lower limit value is allowed, so reverse scaling can also be carried out.
Also, the scale can be enlarged by the upper-and lower-limit width speci-
fied for each data item. The following example shows scaling of the read-
ing side manipulated variable.

Transfer output

(mA)
Reverse scaling
20
4
Transfer output
Transfer
upper limit: 0
output lower
limit: 100
Symbol
Multi-SP function
Event input assignment 1
Set point 0
Set point 1
Transfer output type
Transfer output upper limit
Transfer output lower limit
SP
SP
ramp
OFF
ON
Transfer output
(mA)
20
4
Manipu-
0
lated
Transfer
variable
output lower
(%)
limit: 10
Parameter Name: Mode
: Option
: Option
: Level 1
: Level 1
: Option
: Option
: Option
Time
Enlarged scale
Manipulated
variable (%)
100
Transfer
output upper
limit: 80
Application
Event input functions
Event input functions
Multi-SP
Multi-SP
Transfer output designation
Transfer output scaling