CHAPTER 4 APPLIED OPERATION

4.4 Program Operation

JHold/advance
4–10
• Steps in currently executing programs can be forcibly stopped (Hold)
and advanced (Advance).
• Hold and Advance operation is according to the following procedure:
Run in level 0 mode
Check step No.
Hold?
Y
Hold = ON
End of hold?
End
Hold = OFF
Advance
Y
Advance = ON
Continue
End of advance
End
End: To program operation
• Execute hold/advance operation while making sure the step No. in the
step No. monitor" parameter (level 0 mode).
• When the hold" parameter (level 0 mode) is set to 
counting is paused (held), and the HOLD" LED lights. [
SP appear alternately on the No.2 display when in the PV/Present SP"
parameter.
• Hold is canceled time counting is restarted by one of the following condi
tions: hold" parameter = 
ing advance instruction
• Each time that advance" parameter (level 0 mode) is set to 
the program advances one step. With each step advance, the Advance"
parameter setting returns to 
• If the advance function is executed with the program in a hold state, the
hold state is continued in the next step.
N
Continue
N
: OFF", Run, Reset, End operation us
: OFF".
: ON", step time
] and the
: ON",