CHAPTER 3 BASIC OPERATION
Setting Example
1 second min.
1 second min.
1 second min.
3–6
In this example, let's check the input type and temperature units, and shift
the lower limit by 1_C and the upper limit by 3_C.
input type"
temperature unit"
input shift upper limit"= 3.0"
input shift lower limit" = 1.0"
(1) Select the menu display, and select
or
keys. For details on selecting the menu display, see page
1 10.
(2) Press the
key for one second minimum to enter the setup mode.
The top parameter in the setup mode
This parameter is factory set to 2: K1".
(3) Press the
key to fix the set value. The display changes to
_C/_F selection" parameter. This parameter is factory set to : _C".
(4) Select the menu display, and select
or
keys.
(5) Press the
key for one second minimum to enter the level 2 mode.
The top parameter in the level 2 mode [
rameter) is displayed.
(6) Press the
key until [
is selected. This parameter is factory set to 0.0".
(7) Press the
key until 3.0" is displayed.
(8) Press the
key until [
is selected. This parameter is factory set to 0.0".
(9) Press the
key until 1.0" is displayed. This sets the input shift
upper limit" and input shift lower limit" values.
= 2: K1"
= _C"
: setup mode" using the
: input type" is displayed.
: level 2 mode" using the
] (input shift upper limit" parameter)
] (input shift lower limit" parameter)
:
] (local/remote" pa