Batch write (command: 1613)

Write data to the buffer memory of the host station (supported device).
Do not write any data in "System area" or "Write-protect area" in the buffer memory.
Writing data to the "System area" or "Write-protect area" may cause malfunction of the programmable
controller system.
Message format
The following shows the message format of the request data and response data of the command.
■Request data
Command
Subcommand
■Response data
There is no response data for this command.
Data specified by request data
■Command
ASCII code
1
6
1
3
31
36
31
33
H
H
H
H
■Subcommand
ASCII code
0
0
0
0
30
30
30
30
H
H
H
H
■Start address
Specify the buffer memory start address to be written. (Page 153 Start address)
■Word length
Specify the word length of the buffer memory to be written. (Page 154 Word length)
Specification range: 1H to 1E0H(480)
■Write data
Specify the data to be written in the buffer memory. (Page 154 Read data, write data)
Specify the access range within the range of buffer memory.
(Start address + Word length -1)  Buffer memory range
Word
Start address
Write data 1
length
Binary code
13
16
H
H
Binary code
00
00
H
H
Write data n
10 BUFFER MEMORY ACCESS
157
10.1 Buffer Memory