File name of MELSEC-Q/L series module (Number of characters and file name)
For the data other than response data of read directory/file information (command: 1810), specify with number of characters
and file name character string.
Use the subcommand '0000' or '0004'.
The file name and the extension are specified as a variable length character string with a period inserted between them.
Specify the length of character string with "number of characters". (Page 200 Number of characters)
ASCII code
Number of characters
File name + "." + Extension
(4 digits)
(Variable length)
Specify "File name" + "Period (2EH)" + "Extension" in ASCII code during data communication in binary code as well.
Ex.
File name and the extension are "ABC.QPG". (7 characters including a period)
ASCII code
0
0
0
7
A
B
C
30
30
30
37
41
42
43
H
H
H
H
H
H
Binary code
Number of characters
(2 bytes)
Binary code
.
Q
P
G
07
00
2E
51
50
47
H
H
H
H
H
H
File name + "." + Extension
(Variable length)
A
B
C
.
Q
P
G
41
42
43
2E
51
50
47
H
H
H
H
H
H
H