Network No., PC No.

Specify the network No. and station No. that are set with the parameters for the access target network module.
Specify a fixed value when accessing the connection station.
Specify the network No. with the value shown below.
Specifying improper value may result in no response returned.
Accessing the connected station (host station)
Specify '0' for the network No., and 'FF' for the PC No.
External device
■When using the on-demand function
Specify '0' for the network No., and 'FE' for the PC No.
(Page 280 On-demand function)
Accessing multidrop connection station
Specify '0' for the network No., and 'FF' for the PC No.
External device
Accessing other stations via network
Specify the network No. and station No. of an access target.
Access target
Other station of which station No. is set
Specified control station/master station
Current control station/Master station
*1 Access the station set as a control station/master station by parameters.
*2 Access the station which is operating as a control station/master station.
External device
6 ACCESS ROUTE SETTINGS
52
6.2 Details of Setting Data
Connected station
:Access target station
(Host station)
Multidrop connection
Network No.
01H to EFH (1 to 239)
Stations with network No.240 to 255 are not accessible.
*1
*2
Connected station
(Host station)
Network
No.n
:Access target station
Other stations
:Access target station
PC No.
01H to 78H (1 to 120)
7DH
7EH