Format 4 - Mitsubishi Electric MELSEC IQ-R series Reference Manual

Programmable controller
Hide thumbs Also See for MELSEC IQ-R series:
Table of Contents

Advertisement

Format 4

Message format
■Request message
Control code
ENQ
05
H
■Response message (Normal completion: Response data)
Control code
Frame ID No.
STX
02
H
■Response message (Normal completion: No response data)
Control code
Frame ID No.
ACK
06
H
■Response message (Abnormal completion)
Control code
NAK
15
H
Setting data
Set the following items.
Item
Control code
(ENQ, STX, ACK, NAK, ETX, CR, LF)
Frame ID No.
Access route
Request data
Response data
Sum check code
Error code
4 MESSAGES OF SERIAL COMMUNICATION MODULE
32
4.2 Message Formats of Each Protocol
Frame ID No.
Access route
Sum check range
Access route
Sum check range
Access route
Frame ID No.
Access route
Description
A code is defined for control.
Specify the frame to be used.
Specify the access route.
Set the command that indicates the request content. Refer to "Request
data" rows of each command.
Store the read data for the command. Refer to "Response data" rows of
each command.
The value of the lower one byte (8 bits) of the additional result regarding
the data in the sum check target range as a binary data.
Error code indicates the content of occurred error.
Request data
Sum check code
Control code
Response data
ETX
03
H
Control code
CR
LF
0D
0A
H
H
Control code
Error code
CR
LF
0D
0A
H
Control code
CR
LF
0D
0A
H
H
Control code
Sum check code
CR
0D
H
H
Reference
Page 34 Control code
Page 36 Frame ID No.
Page 45 ACCESS ROUTE
SETTINGS
Page 62 COMMANDS AND
FUNCTIONS
Page 36 Sum check code
Page 38 Error code
LF
0A
H

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsecq seriesMelsec l series

Table of Contents