Mitsubishi Electric MELSEC IQ-R series Reference Manual page 382

Programmable controller
Hide thumbs Also See for MELSEC IQ-R series:
Table of Contents

Advertisement

Monitor (command: ME)
Monitor the registered extended file registers.
■Message format
• Request data
M
E
Message wait
4D
45
H
H
• Response data
Monitoring result ( For the
number of device points )
The value of read device is stored in word units. (Page 74 Read data, write data)
■Data specified by request data
• Command
ACPU common
M
E
4D
45
H
H
• Message wait: Specify the delayed time of the response transmission. (Page 347 Message wait)
■Communication example
Monitor data of 4 points (4 word) specified with monitor data registration under the following conditions.
• Message wait: 0 ms
• Registered devices for monitoring: R1234 of block number 5, R2345 of block number 6, R3055 of block number 15, and 4-
point of R8000 of block number 17.
(Request data)
Message wait
0
M
E
4D
45
30
H
H
H
(Response data)
Monitoring result ( For the number of device points )
3
5
0
1
4
F
(Decimal : 13569) (Decimal : 20315) (Decimal : 366)
33
35
30
31
34
46
H
H
H
H
H
H
(R1234 in No.5)
(R2345 in No.6)
17 COMMUNICATING USING 1C FRAMES
380
17.5 Read and Write Extended File Register
5
B
0
1
5
0
1
C
(Decimal : 366)
35
42
30
31
35
30
31
43
H
H
H
H
H
H
H
H
(R3055 in No.15) (R800 in No.17)
2
D
32
44
H
H

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsecq seriesMelsec l series

Table of Contents