■Data communication in binary code
• Device number: Send 4-byte numerical values from the lower byte (L: bits 0 to 7).
• Device code: Send 2-byte numerical values from lower byte (L: bits 0 to 7).
Ex.
Data register (D) 1234 (device number is decimal)
Convert a device number to hexadecimal. '1234' (decimal)'4D2' (hexadecimal)
ASCII code
4
4
2
0
0
34
34
32
30
30
H
H
H
H
H
For the values of each device code, refer to the following section.
: Space
Device name
Input
Output
Internal relay (include in latch relay and step relay)
Annunciator
Link relay
Timer
Counter
Data register
Link register
File register
Access the devices within the range that can be used in the access target CPU.
For the accessible device range, refer to the following section.
Page 399 Accessible device range
• For word unit specification, the head device number of bit device must be specified in multiple of 16.
• For special relay M9000 or later, (9000 + multiple of 16) can be specified.
18 COMMUNICATING USING 1E FRAMES
398
18.4 Read and Write Device Memory
0
0
0
0
4
D
2
30
30
30
30
34
44
32
H
H
H
H
H
H
H
Symbol
X
Y
M/L/S
F
B
Current value
T
Contact
Coil
Current value
C
Contact
Coil
D
W
R
Binary code
D2
04
00
00
20
44
H
H
H
H
H
H
Type
Representation
Bit
Hexadecimal
Bit
Hexadecimal
Bit
Decimal
Bit
Decimal
Bit
Hexadecimal
Word
Decimal
Bit
Decimal
Bit
Decimal
Word
Decimal
Bit
Decimal
Bit
Decimal
Word
Decimal
Word
Hexadecimal
Word
Decimal
Device code
X
5820H
Y
5920H
M
4D20H
F
4620H
B
4220H
TN
544EH
TS
5453H
TC
5443H
CN
434EH
CS
4353H
CC
4343H
D
4420H
W
5720H
R
5220H