Remote Pause (Command: 1003) - Mitsubishi Electric MELSEC IQ-R series Reference Manual

Programmable controller
Hide thumbs Also See for MELSEC IQ-R series:
Table of Contents

Advertisement

Remote PAUSE (command: 1003)

Perform remote PAUSE for the access target module.
The command can be executed when the switch of the access target module is RUN. In the STOP status, the
command is completed normally, however, the access target CPU will not be in PAUSE status.
Message format
The following shows the message format of the request data and response data of the command.
■Request data
Command
Subcommand
■Response data
There is no response data for this command.
Data specified by request data
■Command
ASCII code
1
0
0
3
31
30
30
33
H
H
H
H
*1 For C24, the additional code is added. (Page 35 Additional code (10H))
■Subcommand
ASCII code
0
0
0
0
30
30
30
30
H
H
H
H
■Mode
Select the operation when the request target module is already in remote operation by other device. (Page 167 Mode)
• 0001H: Do not execute forcibly
• 0003H: Execute forcibly
Communication example
Remote PAUSE is performed when the mode is set to "Do not execute forcibly".
■Data communication in ASCII code
(Request data)
1
0
0
3
0
33
31
30
30
30
H
H
H
H
H
■Data communication in binary code
(Request data)
03
10
00
00
01
H
H
H
H
H
11 CONTROL MODULE OPERATION
176
11.2 Remote Operation
Mode
Binary code (for C24)
03
H
Binary code
00
H
0
0
0
0
0
0
1
30
31
30
30
30
30
30
H
H
H
H
H
H
00
H
*1
DLE
10
10
H
H
00
H
H
Binary code (for E71)
03
10
H
H