Data to be specified
■Extension specification
Specify the access target network No. in hexadecimal.
• ASCII code: Specify J (4AH) at the head of data. Convert the numerical value to 3-digit ASCII code (hexadecimal), and
send it from the upper digits.
• Binary code: Send 2-byte numerical values from the lower byte (L: bits 0 to 7).
Ex.
For network No.8
ASCII code
J
0
0
8
4A
30
30
38
H
H
H
H
Using the index register of CPU module, the access target network No. can be specified indirectly.
Page 446 Access to index the network No. and start input/output number
■Device code and device number
Specify the following devices. (Page 67 Devices)
• Link input (X)
• Link output (Y)
• Link relay (B)
• Link special relay (SB)
• Link register (W)
• Link special register (SW)
For the values of device codes, refer to the following section.
Page 70 Device code list
Using the index register of CPU module, the access target device number can be specified indirectly.
Page 447 Access to index the device number
Device extension specification example
Access W100 (J1\W100) of network No.1 by specifying subcommand 0080.
■Data communication in ASCII code
Subcommand
specification
0
0
8
0
0
0
J
30
30
38
30
30
30
4A
H
H
H
H
H
H
H
■Data communication in binary code
Device
Subcommand
number
80
00
00
00
00
01
00
H
H
H
H
H
H
H
Binary code
08
00
H
H
Extension
Device
code
0
0
1
0
0
0
W
30
30
31
30
30
30
57
2A
H
H
H
H
H
H
H
Device
Extension
code
specification
B4
00
00
01
00
F9
H
H
H
H
H
H
Device number
*
0
0
0
1
0
0
0
30
30
30
31
30
30
30
H
H
H
H
H
H
H
Appendix 1 Read/Write by Device Extension Specification
0
0
30
30
H
H
H
APPENDICES APPENDIX