Mitsubishi Electric MELSEC IQ-R series Reference Manual page 113

Programmable controller
Hide thumbs Also See for MELSEC IQ-R series:
Table of Contents

Advertisement

■Device
Specify a device to be written. (Page 67 Devices)
Specify a bit device.
■Set/reset
Specify the ON/OFF status of bit devices. (Page 80 Set/reset)
The number of points equivalent to the specified "Number of bit access points" is specified for "Device" and
"Set/reset", respectively.
Communication example
Turn M50 OFF, and turn Y2F ON. (Subcommand: for MELSEC-Q/L series)
■Data communication in ASCII code
(Request data)
Subcommand
1
4
0
2
0
0
0
31
34
30
32
30
30
30
H
H
H
H
H
H
H
■Data communication in binary code
(Request data)
Number of bit
access points
Device number
Subcommand
02
14
01
00
02
32
00
H
H
H
H
H
H
H
Number of
Device
bit
Device number
code
access points
1
0
2
M
*
0
0
0
31
30
32
4D
2A
30
30
30
H
H
H
H
H
H
H
Device
Device
Set/reset
Set/reset
code
code
Device number
00
90
00
2F
00
00
9D
01
H
H
H
H
H
H
H
H
Device
Set/reset
code
0
5
0
0
0
Y
*
30
35
30
30
30
59
2A
30
H
H
H
H
H
H
H
H
Set/reset
Device number
0
0
0
0
2
F
0
1
30
30
30
32
46
30
31
H
H
H
H
H
H
H
H
8 DEVICE ACCESS
8.3 Random Read and Write
8
111

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsecq seriesMelsec l series

Table of Contents