7.1.1 EN54 Requirements

Every HONEYWELL panel is factory-
configured with two default Control Matrix
entries.
Any alarm input anywhere on the system will
cause all bell devices, and those internal
sounder circuits configured as sounders, to
operate immediately in 'steady' mode (i.e. they
are switched on to sound continuously).
'
'
The EVACUATE function will operate all BELL
circuits.
Note: Sounders 3 and 4 will only be activated
if they are configured as sounder
outputs and not relays.
IMPORTANT - EN54 COMPLIANCE
The default entries may not be appropriate to
your installation. However, if you delete either
or both defaults it is then your responsibility to
ensure that the installation complies with the
requirements of EN54-2.