Panel Settings; Internal Buzzer Options - Honeywell XLS80e Manual

Panel configuration
Table of Contents

Advertisement

XLS80e Fire Alarm Control Panels
Enabling ENGINEER-
indication of FAULT will
EN54-2: 12.10.2
MUTE, the audible
not comply with the
requirements.

11 Panel Settings

This section describes temporary and
permanent panel settings. These settings are
selected from the Panel Settings menu, which
is accessed from the Configuration menu. The
access level is 3A.
All settings are permanent except ENGINEER-
MUTE mode (Section 11.1) and Temporary
BLINK (Section 11.2) which both time out.
The prompt 'Press to confirm changes, X to
cancel' is displayed at the end of each change.
Note: The Passcode Change option on this
menu is described in Section 8.

11.1 Internal Buzzer Options

1 From the Panel Settings menu, select the
Internal buzzer options.
2 Select whether or not the buzzer resounds
if there is a new alarm in the same zone
(panel automatically resounds buzzer if
alarm is from a different zone).
3 Select either NORMAL or ENGINEER-
MUTE mode (in the latter case the panel
status display changes from NORMAL to
ENG.-MUTE).
In ENGINEER-MUTE mode, if a fault occurs
the fault buzzer sounds at a reduced volume.
This TEMPORARY mode lasts for two hours,
after which time the panel reverts to normal
operation. However, if a fault is present on the
system at the end of the two hour period, the
buzzer will not change to steady operation at
this time, but only on the first subsequent fault.
ENGINEER-MUTE applies only to the local
panel except if the panel is connected to the
XLSNET, in which case it applies to all panels
on the network.
91
Honeywell, Issue 9
March 2007