XLS80e Fire Alarm Control Panels
FROM SECTION 7.5.2.1
IF OPTION 7 SELECTED:
IF OPTION 1 (ALARM) IS CHOSEN:

7.6 Defining a Control Matrix Entry

There are two stages to amending/creating a
Control Matrix entry:
a. Create the input definition.
b. Create the output definition.
When amending an existing entry, at each
stage the initially-highlighted item will be that
which is closest to the current entry.

7.6.1 Input Definitions

Select the input from the list. Subsequent steps
depend upon which input is selected.
Configure the zone numbering type in the panel
settings BEFORE creating any Control Matrix
rules (otherwise the rules must be manually
checked to ensure that the correct zones are
referenced). The panel does not perform any
automatic conversion.
It is possible to cross-reference between
network and local zone numbers (see
Section 14.1.2).
7.6.1.1 ALARM
The first display allows definition of the effect
of alarms from Multi-criteria sensors that have
a thermal-only mode:
a. If the first option is selected, then the
Control Matrix input will be activated by any
alarm from the sensor.
b. If the second option is selected, then the
Control Matrix input will be activated only
by a thermal alarm. Any Control Matrix
rules for which the input is normal alarm
from the device will also be activated. This
option applies only to Acclimate and MCS
sensors.
To define the ALARM input:
a. For Multi-critera sensors in Normal alarm
and for all other types of sensor, follow
steps 1 to 12 below.
b. For Multi-critera sensors in Thermal-only
alarm, refer to the description at the end of
this section.
63
Honeywell, Issue 9
March 2007