Honeywell XLS80e Manual page 81

Panel configuration
Table of Contents

Advertisement

IF INPUT WAS NON-FIRE:
IF INPUT WAS:
ALARM (EXCEPT IMMEDIATE)
IF INPUT WAS:
NON-FIRE HOLD mode: RESTART or EXTEND
timer
AFTER A TIME OF DAY OPTION, THIS
COMPLETES THE OUTPUT DEFINITION
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
2b Select the required non-fire (auxiliary
module) action, one of:
a. Aborts the release.
b. Sets system to MANUAL ONLY.
c. Sets system to OFF.
d. Acts as HOLD switch. Timer is either re-
started or extended when HOLD is
released, depending upon the activation
delay setting (step 3). For use with HOLD
modes AHJ and NYC (Section 7.8).
e. Acts as HOLD switch. Timer is paused
when HOLD is operated, and resumes
when HOLD is released. For use with
HOLD modes ULI and IRI (Section 7.8).
f. The LCD displays 'Reserve CO2 Bank
Selected' on the Extinguishing tab.
g. The LCD displays 'Extinguishant WEIGHT
LOSS Indicated' on the Extinguishing tab.
3a Select the delay before the output is
activated. It is not possible to set the delay
to zero.
3b Select the delay before the output is
activated. If left at the default (which is the
value configured in the Panel Settings
menu), the HOLD mode is AHJ. If given a
greater value, the HOLD mode is NYC. It
is not possible to set the delay to zero.
74

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents