Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels

14.2.1 Station Type

All Stations in a Network have a number. When
setting the station type for that number, follow
these rules:
a. Station number zero is always the Master
panel - this cannot be changed.
b. Slave panels can only exist at station
numbers 1 to 7.
c. Repeaters can only exist at station numbers
1 to 31.
d. Slave numbers and Repeater numbers may
be interleaved.
e. The station numbers must be continuous.
The network configuration edit display only
permits the addition of stations to the
network one at a time, in ascending order.
To select the station type:
1 Use the
move the cursor over the station type to be
edited.
2 Select the required type from the list
provided, then press
120
It is recommended that the
station numbering scheme
be kept as rational as
possible.