Manual Override - Honeywell XLS80e Manual

Panel configuration
Table of Contents

Advertisement

XLS80e Fire Alarm Control Panels
THEN
Additional information about time fields
If a 'start time' is earlier than the corresponding
'end time', a 'day' period is assumed; if the 'start
time' is later than the 'end time' the period is
considered to be a 'night' period. If both start and
end times are set to '00:00' the period is regarded
as not in use. If both start and end times are the
same time, other than '00:00', this is a special
program only meaningful in conjunction with
'manual override' (see Section 9.2, Manual
Override).
Where two daily periods are programmed they
may overlap or abut one another without
causing the panel to malfunction. However, this
practice is not recommended as it may be
confusing. Also, if there is an inconsistency
between weekdays and weekends, as regards
the day and night periods, as in the following
example:
-MTWTF-
S - - - - -S
the weekday 'overnight' period is deemed to
end at midnight on Friday and start again at
midnight on Sunday. Again, this type of
combination should be avoided.
Using an existing time-of-day program
1 When the time-of-day display (but not the
Manual Override option) is shown on the
LCD, press
2 Use
and
time-of-day programs, if any. The maximum
number of programs is seven.
3 Press
to select the currently-displayed
program.

9.2 Manual Override

If Manual Override is set to ENABLED in
the-time-of-day program, an additional item
'Time-of-day Program Over-ride' appears on
the User menu (it is available at access level
2 and above).
87
0830-1040 1800-0600
0830-1040 1800-1900
.
to step through the existing
Honeywell, Issue 9
March 2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents