11.3 Number of LOOPS on panel

This setting is required only if the panel has
had a major reconfiguration or has had a
processor card replaced. You may set the
number of loops that the panel expects to find
to a number different from that automatically
determined by the number of loop interface
boards currently fitted.
The third line shows how many loops are
actually fitted (in this example, 6). If you set
the configured number of loops (fourth line) to
a number greater than this, the panel will
indicate SYSTEM FAULT 17 - Loop n Card
Missing.
If you set the number of loops to more than
two, for each loop pair from 3 upwards select
STANDARD if ordinary LIB boards are fitted
or ENHANCED if ELIBs are fitted. If there are
more than 512 monitored points on the system
you must fit ELIBS - in this case select
ENHANCED so that the panel will indicate a
fault if ordinary LIB boards are fitted. This
confirms compliance with EN-54. No fault is
indicated if STANDARD is selected with ELIBs
fitted.
93
EN54-2: 13.7
Maximum of 512
Sensors and/or MCPs
per panel unless
ELIBs are used
Honeywell, Issue 9
March 2007