Panel configuration
Table of Contents

Advertisement

NUMERIC
KEYS, THEN
NUMERIC
KEYS, THEN
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
5.1.2.2 Edit Device Zone or Cell
Zone Number
Enter the zone number within the displayed
range. RANGE! is displayed if the entered
number is out of range. For details of zone
ranges, refer to Section 14.1.2. The 'Internal
Zone no.' is only displayed if network zones
are used, also in this case an error message
is displayed if you try to configure more than
255 zones on a panel.
Reference Number
If network zones are used, a maximum of 99
devices can be placed in the zone. Each device
is identified by a reference number in the range
1 to 99 (i.e. maximum of 99 devices in a zone).
When a device's zone number is configured
the device is automatically given the first
available reference number by default.
To change this default, either enter one of the
unused reference numbers from the display,
or a reference number that is already used by
a device. If the latter is chosen, the option to
swap the number for that device with one of
the unused numbers is provided automatically
(see below). If the swap is not accepted then
the entered number is rejected.
Cell Number
Devices can optionally be placed in a cell in
addition to a zone. Certain Control Matrix
functions can be set to apply to the cell rather
than the zone.
Enter the cell number in the range 1 to 255, or
select 0 if the device is not to be placed in a
cell.
32