Caution - a false indication
of a fully-functional system
is given if the Auto-learn
procedure is used on an
incomplete system.
Input module types are
set to defaults during the
Auto-learn procedure
and may require manual
re-configuration.
Limitations of the Auto-learn Method
If the auto-learn method is used on an
incomplete system it will give the false
impression that the system is fully operational.
In such cases, the auto-learnt data MUST be
checked carefully against the system
specification.
During the auto-learn procedure, input
module logical types are set to defaults.
Modules not conforming to the defaults must
be re-configured using the Manual Learn or
Configure Individual Device procedures.

3.7 Configure Group of Devices

On a configured panel, this configuration
method allows a group of devices at consecutive
addresses to be deleted or all set to the same
type.
Refer to Section 5.2.

3.8 Configure Individual Device

This configuration method requires the user to
select each loop device and set all parameters
and conditions, e.g. sensitivity, time-of-day,
device text, etc. appropriate to it.
It can also be used to add further details to the
configuration resulting from the auto-learn
method.
Refer to Section 5.1.
Note: Sensitivity and alarm verification delay
recommendations are given in
Section 13.