XLS80e Fire Alarm Control Panels

11.21 Alarm Coincidence

This menu may be Panel Settings option 21
or 22, depending upon whether the Day/Night
Modes configuration option is present.
Select the Zones level to be edited (where
'level' indicates the position on the Control
Matrix 'Multiple Zone Coincidence Rule' menu).
It is recommended that the co-
incidence number increases
For the current level, enter the number of
zones that must be in alarm at the Control
Matrix input. Confirm changes, then repeat this
procedure for each level you want to configure;
press
to exit the Zones level setting option.
Select the Devices level to be edited (where
'level' indicates the position on the Control
Matrix 'Select Coincidence Rule' menu).
It is recommended that the co-
incidence number increases
For the current level, enter the number of
devices that must be in alarm at the Control
Matrix input. Confirm changes, then if required
repeat this procedure for the remaining level;
press
to exit the Devices level setting
option.
Select the scope of Device Coincidence when
the Control Matrix input zone selection is ANY
ZONE:
a. The devices must be on the same panel,
or (networked panels) on any panel of the
network. This is the default.
b. The devices must be in the same zone.
Select the scope of Device Coincidence when
the Control Matrix input zone selection is a
range of cells:
a. Two or more devices in alarm in the same
cell. This is the default.
b. Two or more devices in alarm within the
selected range of cells.
106
with the level number.
with the level number.