IF OPTION 2 (CELL/ZONE/PANEL) IS CHOSEN:
(THIS STEP ONLY IF
INPUT WAS 'ANY
ZONE')
(THIS STEP
OMITTED IF SAME
ZONE AS INPUT)
TO NEXT PAGE
Note: There is an operation limitation in using a
module type 'CDI' as an output. For this to
work ensure that the ALARM supervision
option of the module is set to OFF, which
disables its normal function as a CDI input. A
standard CMX module should be used for
this purpose rather than a CDI or ZMX unit;
although the type designation 'CDI' is still
used it is not literally true in this case.
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
7.6.2.2 All Outputs: Cell, Zone or Panel
Note: If no cells are configured (Sections 5.1.2.2/
5.1.4.2) the ZONE or CELL selection
screen is bypassed.
Select ZONE if a specified zone is to be the
output.
Select CELL if a specified cell is to be the
output.
ZONE
1 Select whether the output zone is the same
as the input zone or not.
Note: If network zones are used and the
output zone is the same as the input
zone, the selected zone must be local
to this panel, irrespective of its zone
number.
2 If the output zone is NOT the same as the
input zone, select it (or a range up to 32)
from the displayed list.
Restricted by Type
3 Either select ALL OUTPUT MODULES or
restrict to one type of module. Select the type.
If an output delay is to be imposed, the delayed
outputs to sounders must be separated from
delayed outputs to other kinds of output. Do not
select the type ALL if delays are to be imposed.
If ALL OUTPUT MODULES or ALL SOUNDER
MODULES are selected, the internal sounder
circuits are included in the output category.
Virtual Output Points are included with ALL
OUTPUT MODULES, and with either ALL
SOUNDER MODULES or ALL CONTROL
MODULES depending upon their configured type
(BELL/SOUNDER or CONTROL MODULE).
Note: The above configuration should be used
if a special operation, not covered by
standard CDI configuration, is required.
For resetting standard CDI or ZMX units
only, there is no need to create specific
Control Matrix entries. Instead,
designate the modules as type CTRL
and then individually link to RESET.