XLS80e Fire Alarm Control Panels
MUTE
EXTEND
END DELAY /
SILENCE /
RESET
BUZZER
DELAY
EVACUATE
RESOUND
DAY
FIRE O/P
CHANGE
ZONES IN
MODE
DISABLE
TABS
ALARM
DISABLEMENT
FIRE
TEST
FAULT
POWER
PRE-ALARM
DAY MODE
SYSTEM FAULT
DELAYS ACTIVE
SOUNDER FAULT / DISABLED
TECHNICAL ALARM
FIRE O/P FAULT / DISABLED
FIRE O/P ACTIVE
XLS80e
0
1
2
3
4
5
6
7
8
9
EN54-2/4 1997
3.3 Using the Panel Controls and
Indicators
All of the configuration operations described in
this manual can be done using the panel
pushbuttons and Liquid Crystal Display (LCD),
with no external equipment required.
The panel remains 'on watch' during the
configuration sequence, and will therefore
respond appropriately to any fire or fault
conditions that arise.
The manufacturer recommends that you keep
a secure copy of the system configuration on a
PC as a backup, in case of difficulties in the
configuration sequence.

3.3.1 Pushbuttons

OPERATING PUSHBUTTONS
CHANGE TABS - Scrolls through the tabbed
displays. Refer to Section 4.2 for further
information.
RESET - Restores normal operating status
when all alarm conditions have been removed.
Note: The other operating pushbuttons are not
used during configuration. Their
operation is described in the XLS80e
Series Operating Manual (997-474).
CURSOR AND NUMERIC PUSHBUTTONS
menus. When the panel status is normal and if
the printer is fitted,
Used to: select menu options, select quick
methods of dis/enablement and walk test
cancellation, control the event log display, select
loop device parameters for edit, display existing
time-of-day programs, create a new Control
Matrix entry and select characters during text
editing.
to
- Used to select items and enter
0
9
data on the LCD.
- Used to accept an item or state on the
LCD.
- Used to cancel an item or state on the
LCD.
KEYSWITCH - Setting the keyswitch to the
right has the same effect as entering an
access 2 passcode. Set it to the centre to
deselect access 2.
11
- Used to move around the LCD
advances the printer paper.
Honeywell, Issue 9