XLS80e Fire Alarm Control Panels
ALARM
5.1.2.3 Edit Device Location Text
Edit the text description which is used for the
various tab displays (e.g. fire, fault) and for
printing at the printer. Section 6 describes how
to use the text editor.
5.1.2.4 Edit Sensitivity level and Fault
Supervision
The alarm and pre-alarm sensitivities can be
configured.
The Gas Sensor Interface Alarm, Pre-alarm
and Fault levels are all editable values in the
range 4 to 20mA instead of pre-set levels.
Details are given in Section 5.1.3.3.
Alarm
The illustration shows the alarm sensitivity
selected for edit. Up to 9 pre-set levels are
available
for
Photo/Thermal (MULT) and MCS); for all
sensor types (except MULT and MCS) the
default setting is L5. L1 is most sensitive and
L9 is least sensitive. Refer to Section 13 for
recommendations.
Details of MULTI sensor sensitivity are given
in Section 5.1.3.
Further information about MCS sensors
sensitivity is given in Section 5.1.3.2.
33
each
sensor
(except
Honeywell, Issue 9