Multi, Mcs & Gas Sensitivities - Honeywell XLS80e Manual

Panel configuration
Table of Contents

Advertisement

XLS80e Fire Alarm Control Panels
ILLUSTRATION SHOWS ACCLIMATE CONFIGURED
IN THERMAL-ONLY MODE FOR ALARM.
NORMALLY ACCLIMATE WILL BE CONFIGURED
AT L5 FOR ALARM, AND THE THERMAL-ONLY MODE
WILL BE INVOKED VIA A TIME-OF-DAY PROGRAM
OR VIA THE DAY MODE PUSHBUTTON. SEE
SECTION 9.4.
Software version 4.33 and above:
Default Alarm threshold is L5 for
newly installed multi-criteria sensors
(was L3 on previous versions; if
software is upgraded to 4.33, existing
devices retain this default).
Pre-Alarm threshold value MUST
be LOWER than the Alarm
threshold value to be effective.
THERMAL MODE BY ZONE OPTION IS ONLY
DISPLAYED FOR MULTI SENSORS AND IS ONLY
APPLICABLE FOR ACCLIMATE DEVICES. AN
ACCLIMATE SENSOR SET TO 'YES' WILL BE
INCLUDED IN ANY CONTROL MATRIX ENTRY
FOR WHICH THE INPUT IS NON-FIRE OR TRUE
AND THE OUTPUT 'SET TO THERMAL-ONLY
MODE' INCLUDES THE SENSOR'S ZONE
NUMBER. SEE SECTION 7.6.2.6.
5.1.3 MULTI, MCS & GAS Sensor
Interface Sensitivities
5.1.3.1 Photo/Thermal (MULT) Sensors
Device type MULT applies to the
TC840ME.
ACCLIMATE, has a Thermal-Only mode, i.e.
a mode in which the sensor does not respond
to smoke.
Sensitivity (including Acclimate)
When configuring the Alarm and Pre-alarm
sensitivity for MULT sensors, there are five
sensitivity levels plus Pre-alarm disable (L0) and
(for Acclimate only) the Thermal-Only mode:
Sensitivity
Levels
L1 (Most)
L2
For Pre-alarm Threshold
L3
L4
L5 (Least)
For Alarm Threshold
L6
Thermal-Only mode (Acclimate)
For Pre-alarm to operate, the Pre-alarm
Threshold MUST be set at least one level
below the Alarm Threshold. In Thermal-Only
mode (L6), Pre-alarm applies to both smoke
and heat, unless L6 is linked to Time-of-Day
or Day Mode with Lock Pre-alarm monitoring
not set, in which case there is NO Pre-alarm
in L6 mode.
Thermal Mode by Zone (Acclimate only)
All Acclimate sensors in a zone or range of
zones and configured as described below can
be set to their Thermal-Only mode by the
Control Matrix. To configure an Acclimate
sensor for this action, set its device
configuration option 'Thermal Mode by Zone'
to 'Yes'. Only those Acclimate sensors so
configured will be included in the Control Matrix
output. The default for this option is 'No'.
37
MULT Sensor
Default Settings
Honeywell, Issue 9
March 2007