Honeywell XLS80e Manual page 55

Panel configuration
Table of Contents

Advertisement

FROM PREVIOUS PAGE
NUMERIC KEYS,
THEN
REFER TO SECTION 5.3.5 FOR DETAILS OF
THE END OF THE LEARN PROCESS
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
5 Set the zone into which new sensors or
modules will be placed. If you select the '0'
option:
a. If a newly-learnt device replaces an existing
device of the wrong type, it is placed in the
same zone as the existing device.
b. If the newly-learnt device is at a previously-
unconfigured address, it is placed in the
same zone as the nearest existing (i.e.
before the learn process started) device
with an address lower than the new device,
or in zone 1 if there is no such device.
Addressing is carried over from loop to loop
and from modules to sensors.
c. GAS sensors require at least three
consecutive sensor addresses. If an IIG-1
or IIG-4 device is found within the address
range selected for Auto-learn, the next two
addresses are automatically skipped and
any devices already found at those
addresses are deleted. This happens
even if one or both of the next two
addresses is outside the selected range.
Note: If network zones are being used and the
learnt devices need to be split between
zones (because max. of 99 devices per
network zone), new zones are
automatically assigned, numbered
upwards and starting with the entered
zone number.
6 Press
to begin the auto-learn process.
7 As the learn process progresses, the status
is displayed. The top two rows are always
displayed. The remaining rows are
displayed when a new or changed device
is found. If an expected device is not found,
the bottom row displays DELETED.
Note: If REJECT was selected in step 3, the
message 'Unterminated Module -
rejected' is displayed. If WARN was
selected, the options to REJECT or
ACCEPT are provided. There are two
ACCEPT options as described in
step 3c.
48