4.2 Tabs

When tabs are displayed, use the CHANGE
TABS key to scroll through the tabs and thus
display the corresponding data.
The tabs are (in descending order of priority):
EXTINGUISHING (if about to release;
otherwise priority is below FIRE)
FIRE
TECH. ALARM
PRE-ALARM
FAULT
DISABLE
TEST
EVACUATE
AUX
MAINT (access level 3 only unless Maintenance
Urgent)
USER (at access level 2) or
SERVICE (at access level 3)
The tabs are displayed in this order from left
to right. All the tabs display events except for
the USER and SERVICE tabs, which display
menus. The current tab is that without a line
above it.
Note: If there is insufficient room to display all
the tabs, the ones at the right (those with
the lowest priority) are omitted.
Use ZONES IN ALARM to go directly to the
FIRE tab without scrolling through the other
tabs. If there is more than one zone in alarm,
subsequent operations of the ZONES IN
ALARM pushbutton scroll through these
zones.
Note: If the FIRE tab is present but not
selected, and for 20 seconds none of
the panel pushbuttons are pressed, the
FIRE tab is then selected automatically.
Note: If the SERVICE or USER tab is selected,
and for 2 minutes none of the panel
pushbuttons are pressed, the tab is
deselected automatically and all
passcodes are cancelled (except the
access level 2 passcode when the
keyswitch is set to the horizontal
position).
21
Honeywell, Issue 9
March 2007