Honeywell XLS80e Manual page 31

Panel configuration
Table of Contents

Advertisement

Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
Maint Tab
This displays the maintenance status of any
MCS and Acclimate sensors installed on the
loops. If the panel is connected to an XLSnet
network and more than one panel contains
sensors requiring maintenance, an option to
choose the panel is provided.
There are four status messages:
a. Maintenance Urgent. Indicates drift limit
condition and is accompanied by a
SENSOR FAULT fault message.
b. Maintenance Alert. Indicates drift limit or
continuous IR saturation condition.
Maintenance Alert is also displayed in
respect of any Acclimate sensors.
c. 6 months to cell life expiration (MCS4 only).
d. IR light saturation condition (MCS4 only).
If a sensor returns from a maintenance
condition to its normal state, the display is as
shown opposite.
From the 'Maint.' tab, when the status of an
individual sensor is displayed, press the
pushbutton to display a Select Action menu
(the illustrations opposite cover all possible
options - in practice not all options may be
present, see below for details). The options are:
a. Actions on this sensors's LEDs. The LED
can be set to OFF, 1-second pulsing, or ON
STEADY. This option is always available.
b. DELETE ALL restored sensors from log.
The maintenance status is stored in a log
(capacity 100 records per panel). This
option delete records from the log for all
sensors that are in the 'Restored from
Maintenance Condition' state. Available
provided at least one sensor is in this state.
Note: Use the Historic & Data Log Tool
(supplied with the Windows Support
Tool) to access the log.
c. DELETE this sensor from log. Available
only if the current sensor is in the 'Restored
from Maintenance Condition' state.
d. DISABLE THIS DEVICE. Always available,
may be ENABLE THIS DEVICE depending
upon disablement status of current sensor.
e. PRINT Sensors in Maint. condition. Always
available.
f. Select another Panel. Displays the Select
Panel option. Only available if the panel is
connected to an XLSnet and more than one
panel contains sensors requiring maintenance.