11.19 Day/Night Modes Configuration

This menu option is only available if a Fire
Output
has
Section 11.18).
configuration of the Day Mode two-stage
investigation time, which delays operation of
the fire output(s) (does not delay sounders,
use the Control Matrix to do this). The first-
stage time is configured in seconds and is
initiated by an alarm while Day Mode is active
(set by the DAY MODE pushbutton; Day Mode
can also be configured to occur automatically
by a time-of-day program). The second-stage
time is configured in minutes and is initiated
when the EXTEND DELAY pushbutton is
pressed while the first-stage time is active; it
replaces (is NOT added to) the first-stage time.
Set the Day Mode delays as follows:
1 Enter the required first-stage investigation
time.
2 Enter
the
investigation time.
3 Select whether a change of state at Input 2
of the panel results in a change from Day
Mode to Night Mode (option 2), or a Day/
Night Mode change in either direction
(option 3) or has no effect (option 1).
4 Select whether Day Mode can only be set
active by the DAY MODE pushbutton, or
whether a time-of-day program will set Day
Mode at specified times of day.
5 If a time-of-day program is to be used, set
the required times in the manner described
in Section 9. In this case there are only two
time fields for each day set, not a pair of
start and end times. Also, there is no 'level'
adjustment and no 'Manual Override'.
6 Confirm the changes.
104
been
configured
(see
The
settings
allow
required
second-stage
EN54-2: 9.1.2
Disablement and
re-enablement MUST be
a manual operation at
access level 2.

Hide quick links: