4.3.4 Serial interface

The serial interface on the Basic module may be configured as a TTY interface (20 mA) or as an RS485
interface.
The required interface to connect external devices is selected by the Service software tools 8000
from Version V1.06.
TTY interface
V62 V63
reversed
TxD
Polarity
A
B
A
RxD
TxD
TTY
Tx -
Tx +
Rx -
external devices
Fig. 35: TTY interface
FB 798951.GB0 / 01.09
These four terminals may be used for connecting an
external device, e.g. a protocol printer or the kit for a
redundant transmission path (Part No. 784749*), via the
TTY interface (20 mA).
The cable length between external device and interface
must not exceed 1000m.
In operation (green LED)
If wired correctly, the green LED (TxD) will blink at the
transmission frequency to provide visual indication of proper
interface wiring.
B
Reverse polarity indicator (red LED)
If the connection cables are transposed at the terminals, red
LED (Reversed polarity) will light up.
Rx +
Fire Alarm Control Panel IQ8Control C/M
*
This option may be installed inside the FACP housing with the Top-hat
rail mounting kit (Part No. 788652) – refer to Chapter Options -.