Fire Alarm Control Panel IQ8Control C/M
6

Relay module

6.1

3-relay module / 3-relay common trouble module

Micro module for activating external devices (not potential free) such as a flashing lamp or siren, with monitoring
capability. You may connect up to three external devices to this micro module.
Relay assignment is programmed with the service PC and Programming software tools 8000 from version
V1.06R001 software. For each relay, you may enter a specific additional text comprising 25 characters per line
for output on the alphanumeric display and protocol printer.
1 2 3 4 5 6 7 8 9 1 0
S 1
L E D
Fig. 64: 3-relay module / 3-relay common trouble module
X 1
64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
K1, K2, K3 K 1 (for 3-relay common trouble module type used as common trouble relay)
K 2 and K 3 freely programmable, max. contact rating 30 V DC /1 A
coding switch for selecting monitored / non- monitored setting, or for special application
S1, S2
TEST
Test socket for in-factory adjustments only!
LED
No indicator function (in-factory testing purposes)
F1, F3, F5
Electronic fuse (multifuse): to reset, de-energise for approx. 30 seconds at the relevant screw
terminals on the terminal card
76
W i t h t h e 3 - r e l a y m o d u l e ( 7 8 7 5 3 2 ) , r e l a y K 1 i s c o n n e c t e d
a s c o m m o n t r o u b l e r e l a y , t h a t i s , i n t h e n o r m a l a c t i v a t e d .
1
2
F 5
K 3
K 2
S 2
3 - r e l a y m o d u l e / 3 r e l a y c o m m o n t r o u b l e m o d u l e
7 8 7 5 3 1
3 R Ü
F 3
F 1
K 1
7 8 7 5 3 2
3 R Ü S
X 1
FB 798951.GB0 / 01.09