Honeywell IQ8Control C Installation Instruction page 38

Fire alarm control panel
Hide thumbs Also See for IQ8Control C:
Table of Contents

Advertisement

Fire Alarm Control Panel IQ8Control C/M
1.
Open panel housing
2.
Set DIL switch S2 (1+2) on the Basic module in Pos. ON (LED V50 lits).
3.
Press reset button
4.
Wait until FACP is resetted and the display message „Servicemode" appears.
5.
Connect USB cable (Part No. 789863) to the USB-connector of the FACP IQ8Control an.
6.
Start tools 8000 software on the Service PC and select >Tools / actualize panel software<.
7.
After the firmware update the message >Update successful< appears on the Service-PC
8.
Remove USB-plug from the Basic module and set DIL-switch in position OFF
be automatically resetted and returns to the normal operation mode.
38
FACP reset
the FACP IQ8Control will
FB 798951.GB0 / 01.09