Fire Alarm Control Panel IQ8Control C/M
5.1.3 Technical Data Analog loop module
Internal voltage supply
Quiescent current
(with 127 loop devices)
Emergency operation
Terminals
Recommended connecting
cable
•
The permitted loop length depends on the number and type of the loop devices and may differ
from the max. loop length.
•
max. 2 analog loop modules Part No. 804382 / 804382.10 / 804382.D0 per IQ8Control C as well
as max. 4 or 6 modules per IQ8Control M
•
Part No. 78 4382 / 78 4382.10 / 78 4382.D0
Analog loop module to connect Fire detectors and esserbus
voltage 27.5 V must be selected via the jumper on the power supply module Part No. 802426 of
the FACP
•
Part No. 80 4382 / 80 4382.10 / 80 4382.D0
Analog loop module to connect Fire detectors and esserbus
The required loop voltage 42 V must be selected via the jumper on the power supply module
(Part No. 802426) of the FACP.
Maximum line lengths based on the total load factor of a loop
FACP
max. loop lenght
up to 700 m
800 m
1000 m
1100 m
1300 m
1500 m
1600 m
2000 m
up to 3500 m
up to 700 m
800 m
1000 m
1100 m
1300 m
1500 m
1600 m
2000 m
up to 3500 m
68
Part No. 784382 / 784382.10 /
784382.D0 (esserbus
Internal +12 V and +27,5 V
60 mA @ 12 V
yes
removable, for max. 1,5 mm
gauge
•
Telephone cable I-Y (ST) Y n x 2 x 0.8mm with special designation or
fire detection cable
•
Loop resistance 75 Ω @ 1000 m loop length
(measured from terminal A+ to B+)
•
Total loop resistance max. 130 Ω (measured from terminal A+ to B+)
•
Up to 3500 m total loop length is possible for IQ8 fire detectors or alarm
devices with consideration of the load factor
Loop 1
Loop 2
91 to 96
91 to 96
85 to 90
85 to 90
73 to 78
73 to 78
67 to 72
67 to 72
61 to 66
61 to 66
55 to 60
55 to 60
49 to 54
49 to 54
1 to 48
1 to 48
0
0
46 to 48
46 to 48
40 to 45
40 to 45
35 to 39
35 to 39
34 to 36
34 to 36
31 to 33
31 to 33
28 to 30
28 to 30
25 to 27
25 to 27
1 to 24
1 to 24
0
0
Part No. 804382 / 804382.10 /
®
)
804382.D0 (esserbus
Internal +12 V and +42 V
2
wire
removable, for max. 1,5 mm
gauge
analog loop module (esserbus
®
-transponder. The required loop
analog loop module (esserbus
®
-transponder and alarm devices.
Loop 3
Loop 4
91 to 96
91 to 96
85 to 90
85 to 90
73 to 78
73 to 78
67 to 72
67 to 72
61 to 66
61 to 66
55 to 60
55 to 60
49 to 54
49 to 54
1 to 48
1 to 48
0
0
46 to 48
46 to 48
40 to 45
40 to 45
35 to 39
35 to 39
34 to 36
34 to 36
31 to 33
31 to 33
28 to 30
28 to 30
25 to 27
25 to 27
1 to 24
1 to 24
0
0
®
PLus)
60 mA @ 12 V
yes
2
wire
®
)
®
-PLus)
Loop 5
Loop 6
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
46 to 48
46 to 48
40 to 45
40 to 45
35 to 39
35 to 39
34 to 36
34 to 36
31 to 33
31 to 33
28 to 30
28 to 30
25 to 27
25 to 27
1 to 24
1 to 24
0
0
FB 798951.GB0 / 01.09