Cable glands

Lead the 230V main power cord through the wall and the cable entry
illustration). Fasten it using appropriate devices, e.g. plastic cable straps.
Make sure that the mains and signal cables don't interfere with the rear panel of the cabinet or the cabinet frame
which is mounted on the rear panel.
Signal cables must only be led through the other cable entries
IQ8Control
Fig. 20: Cable glands
Danger - Electrical shock !
Disconnect all power from the panel before carrying out any installation work. The panel may only be
operated while the cabinet is closed. Operation is not allowed while the cabinet is open.
Risk of short circuit
All voltage and signal lines connected to the Basic module must be secured to prevent slipping by
using a suitable attachment materials such as plastic cable binders. Make sure the voltage cable will
not move and touch the signal lines (SELV). Work on the FACP IQ8Control may only be carried out
when it is de-energised (mains and emergency power supply).
Insulation of connecting cable
Make sure to lead all cables complete with their outer sheaths intact into the cabinet. Only remove the
insulation from those sections which are inside the cabinet.
3.8

Panel buzzer

If required the internal panel buzzer may be disabled with the solder jumper BR2 on the rear side of the
operating panel PCB.
BR2
BR2
closed, buzzer enabled (factory setting)
BR2
open, buzzer disabled
If the buzzer is permanently disabled (BR2 open), the transmission of this audible warning signal to
must be ensured (e.g. by indicating this condition at a panel within the network)!