Honeywell IQ8Control C Installation Instruction page 35

Fire alarm control panel
Hide thumbs Also See for IQ8Control C:
Table of Contents

Advertisement

BR2
Solder jumper to set whether the two batteries are connected and the monitoring for the free
battery connection should be switched off.
Open (default)
closed
BR 3 / BR 4
Solder/jumper for wiring the LCD indicator panel via the RS 485 interface
BR7
Solder jumper for enabling an internal printer
D21
Integrated circuit, replacement not required
F1
Mains fuse T1.25A H / 230 V DC
F2
Fuse T2,5A
F3
Fuse T2,5A
F4
Fuse T2A
V46
lights during emergency operation
S2
DIL switch
V62 / V63
LED V62 lits red
LED V63 lits green
X1
Transformer connection (primary site)
X2
AC mains connector terminal L1/U, N, PE; for cable with 1,5 - 2,5 mm
X3
Connector for the micro module slot, the internal serial interface TTY / RS 485-1, the common
trouble relay, inputs I1 and I2 , the control voltage for the built-in printer and the supply voltage
(12 V DC, Ub
The RS 485-2 interface connection is not supplied!
X7/X8 (LED V2)
Cover contact connection (FACP housing). LED V2 lights while the cover is open.
X9-A, 10-B
Connector for the power supply module (Part No. 802426 from Index G)
X11-A, 12-B
Micro module slot for a selectable micro module
Connector for the built-in printer via a 26 pole ribbon cable
X23
(For 19" racks the ribbon cable Part No. 750756 max. 50 cm or 750757 max. 120 cm is required)
X24
Connector for the operation panel via a 40 pole ribbon cable
X27, 28, 29, 30
Jumpers to configure the EMI protection for the terminals if an essernet
connected.
X31
Connector for the Service-PC (optional panel interface required)
X32
X34
X33/35
Jumper for the RS 485-2 interface (do not alter position)
X45, X46
Jumper for factory settings only ( do not alter ISB)
USB
Connector for the service-PC and USB-Interface for a System software update.
Ethernet, Phone box,
HW FAILSAFE, USL,
Internal devices and terminals for future system developments
ISB, Smart card
FB 798951.GB0 / 01.09
Connection of two batteries >Battery 1+2<
Connection of a single battery only to connector >Battery 1<.
(The power charge and monitoring of >Battery 2< is disabled)
battery charge current, battery 1
battery charge current, battery 2
12 V DC supply voltage +Ub
Operating mode "OFF" (factory default)
Service mode "ON" (software update via USB interface)
Reversed polarity of the connected TTY cable
to check data communication if the TTY-interface is enabled
) for external equipment
ext
1
2
Pos 1/2
RS485-1 terminating resistance activated
3
1
2
Pos 2/3
RS485-1 terminating resistance not activated
3
1
Pos 1/2
RS485-2 End of line resistor activated
2
(do not alter factory default)
3
1
2
Pos 2/3
RS485-2 terminating resistance not activated
3
Fire Alarm Control Panel IQ8Control C/M
for external devices
ext
Limited functionality of the Panel
2
(#12-14 AWG)
®
micro module is
The RS485-2 interface is
not supplied for this panel
version.
35