4.3.6 Technical data Basic module

Operating voltage
Quiescent current
Emergency mode operation
Fuses
Supply voltage for external devices
Common fault relay
Terminals
- Mains connection
- Communication cables
TTY -interface
or
RS485-1 interface
Do not connect relays (AE) of the FACP with alternating voltage. Even in the case of a >dry relay
contact< it is not possible to switch an external AC-voltage.
Compatibility
FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
: Internal via the power supply module, +5 V DC / + 12 V DC
: approx 215 mA @ 12 V DC without operating module
approx 230 mA @ 12 V DC incl. operating module
approx 295 mA @ 12 V DC incl. operating module ¼ VGA
: available
: F1 = T1,25A H/230 V AC
F2 = T2,5A
F3 = T2,5A
F4 = T2A / 12 V DC
:
max. 12 V DC/ 2A (terminal +Ubext / GND)
: 1 dry change-over contact
Contact rating max. 30 V DC / 1A
Relay operation with common fault programmable in the customer
data
2
:
1,5mm
up to max. 2,5mm
:
removable, max. 1,5mm
:
20 mA, max. 1000m cable length
:
max. 1000m cable length
: Part No. 772481
Basic module IQ8Control C
Part No. 772482
Basic module IQ8Control M
The Basic module is suited for the Fire Alarm Control Panels
IQ8Control C/M with the required power supply module
(Part No. 802426 from index G).
The required loop voltage (27,5 V or 42 V for esserbus
must be selected on the power supply module.
For the Fire Alarm Control Panel system 8000 the basic module
may be used as replacement device. This requires the power
supply module (Part No. 802426 from index G).
mains voltage, primary
battery 1
battery 2
supply voltage
for external devices
2
2
®
PLus)
45