Esserbus; Esserbus ® Analog Loop Module (Part No. 784382 / 784382.10 / 784382.D0) - Honeywell IQ8Control C Installation Instruction

Fire alarm control panel
Hide thumbs Also See for IQ8Control C:
Table of Contents

Advertisement

Fire Alarm Control Panel IQ8Control C/M
®

5.1.1 esserbus

Analog loop module (Part No. 784382 / 784382.10 / 784382.D0)
The analog loop module enables you to connect the analog loop - the esserbus
with Programming software tools 8000 from index V1.06R001.
®
Fig. 54: esserbus
Analog loop module
K2 (B)
K1 (A)
Fig. 55: Analog loop module (Part No. 784382 / 784382.10 / 784382.D0)
Connect cable shielding of the analog loop only at one side.
When using the module in door control systems, place the enclosed labels on or in the FACP
housing (see chapter 11.1).
64-way plug connector to micro module slot of the Basic module, Field device module or
X 1
Extension module
K1, K2
Bi-directional loop interrogation by loop isolators
(K1 = A+, A- / K2 = B+, B-)
LED 1
(SMD) red, flashing
(SMD) red, lit
LED 2
(SMD) yellow, lit
LED 3
(SMD) red, flashing
(SMD) red, lit
LED 4
(SMD) yellow, flashing
(SMD) yellow, flashing rapidly
64
esserbus
®
LED 1
in normal mode in time with communication on the loop
Short circuit on analog loop
Module faulty
+ 24 V supply voltage failure or communication to
control panel processor interrupted
Module in CPU failure mode
(control panel CPU failure)
Processor program running – normal mode
Module in test mode
®
. The analog loop is configured
Fire alarm and extinguishing
computer 8010
X1
LED 2
LED 3
LED 4
FB 798951.GB0 / 01.09