Fire Alarm Control Panel IQ8Control C/M
®
5.1.1 esserbus
Analog loop module (Part No. 784382 / 784382.10 / 784382.D0)
The analog loop module enables you to connect the analog loop - the esserbus
with Programming software tools 8000 from index V1.06R001.
®
Fig. 54: esserbus
Analog loop module
K2 (B)
K1 (A)
Fig. 55: Analog loop module (Part No. 784382 / 784382.10 / 784382.D0)
•
Connect cable shielding of the analog loop only at one side.
•
When using the module in door control systems, place the enclosed labels on or in the FACP
housing (see chapter 11.1).
64-way plug connector to micro module slot of the Basic module, Field device module or
X 1
Extension module
K1, K2
Bi-directional loop interrogation by loop isolators
(K1 = A+, A- / K2 = B+, B-)
LED 1
(SMD) red, flashing
(SMD) red, lit
LED 2
(SMD) yellow, lit
LED 3
(SMD) red, flashing
(SMD) red, lit
LED 4
(SMD) yellow, flashing
(SMD) yellow, flashing rapidly
64
esserbus
®
LED 1
in normal mode in time with communication on the loop
Short circuit on analog loop
Module faulty
+ 24 V supply voltage failure or communication to
control panel processor interrupted
Module in CPU failure mode
(control panel CPU failure)
Processor program running – normal mode
Module in test mode
®
. The analog loop is configured
Fire alarm and extinguishing
computer 8010
X1
LED 2
LED 3
LED 4
FB 798951.GB0 / 01.09