Fire Alarm Control Panel IQ8Control C/M
RS485 interface
An external device, such as an LCD display panel, can be connected to the A/B terminals via the RS485
interface.
1
2
3
A
RS485
1
-
+
A
external device
Fig. 36: RS485 interface
RS 485-1
A/B
Connection of the interface cable – total length max. 1000m
X32
closed
open
RS 485-2
A/B
Do not alter position of the jumpers!
X33/35
Do not connect terminals!
X34
42
X33
X35
1
1
2
2
3
3
X34
X32
1
2
3
B
A
B
RS485
2
B
RS 485 termination resistance activated
RS 485 termination not activated
The RS485 BUS must be connected with an
EOL resistor at both ends of the loop.
If the FACP incl. basic module is the last
device on a loop end, the integrated EOL
resistor can be activated with the X32 jumper.
FB 798951.GB0 / 01.09