Honeywell IQ8Control C Installation Instruction page 109

Fire alarm control panel
Hide thumbs Also See for IQ8Control C:
Table of Contents

Advertisement

9.2
The essernet
®
The essernet
connection of the various units in the network can be checked with this diagnostic line.
®
The essernet
diagnostic line (L:xxx) indicates which connections are functioning correctly and which have
malfunctioned. Non existent units/ control panels are represented by the character "?".
The status display at the beginning of the line (0,S,E or B) indicated whether data calibration is in progress
between two control panels. This is always the case when signals are updated in the essernet
when a switched off control panel is switched back on or when a new control panel is integrated in the essernet
network and its data is automatically updated. Which control panel is conducting this data calibration can be
determined by the two-digit control panel number (part: xx).
Switching on the essernet
Test
Press key
Approx. 5 seconds after switching on, the essernet
Once selected, the diagnostic line remains visibly in the display in all menu levels, for example when changing
to the status display, the installer level or when scrolling the contents of the display, until it is deactivated.
Switching off the essernet
Test
Press key
After approx. 5 seconds, the display of the essernet
Display contents and their significance
0 Zxx Pxx L:00021??????????????????????????
Fig. 97: Display and significance
FB 798951.GB0 / 01.09
®
diagnostic line
®
diagnostic line
Test
®
®
diagnostic line
Test
essernet
®
status list for control panel No. 1 to 31
0 = essernet connection OK
1 = no data from terminal 3/4 (short circuit/open connection)
2 = no data from terminal 1/2 (short circuit/open connection)
9 = no communication between FACP and essernet
? = customer data not programmed
Control number (01 to 31) with which data calibration is in progress
Decimal display (00 to 99) of the communication status (only factory use)
Status of the data calibration
0 = data calibration OK
S = Control panel is transmitting
E = Control panel is receiving
B = Data calibration terminated/faulty
Fire Alarm Control Panel IQ8Control C/M
F4
diagnostic line appears in the display.
F4
®
diagnostic line is switched off.
®
, for example
1
2
®
module
®
109