Fire Alarm Control Panel IQ8Control C/M
Trouble
Possible cause
Code No.
®
esserbus
038
identified fault with its external
voltage.
Communication between
®
esserbus
039
panel has been disturbed for
100 seconds.
Communication between
®
esserbus
transponder 808615 and the
043
8010 fire and extinguishing
panel has been malfunctioned
for over 100 seconds.
Communication between
FACP and esserbus
communication transponder
044
for the 8010 fire and
extinguishing panel has been
malfunctioned.
048
052 / 053
060
Short circuit detected behind
060
the isolator of the
transponder.
Failure of the internal data
062
communication of the
transponders CPU.
Detector data assignment
063
incomplete or EEPROM
failure.
Loop wiring has been
066
changed.
Detector cannot be addressed
with serial number. The
067
detector changed at this
location is faulty or absent.
The detector that was
positioned at this location has
been installed at a different
068
location. One or more
detectors on the loop have
been interchanged.
118
1st. measure
Check whether the external
transponder has
switching voltage of the
esserbus
the correct voltage range.
transponder and
Notify Customer Service.
Check correct functioning of
the 8010 fire and
communication
extinguishing panel. Correct
any malfunctions of the fire
and extinguishing panel and
switch on the esserbus
communication transponder
via the FACP keyboard.
®
Notify Customer Service.
see 001
see 020
see 028
Switch-on transponder or
loop. If error occurs again
refer to 2
Repeat detector data
assignment on the relating
loop.
Connect service PC and
perform configuration check.
Check location to see whether
detector is absent or
improperly installed in
detector base. Switch on loop,
perform test on detector zone.
If this change is desired, you
must activate the >Detector
change< function at the panel.
2nd. measure
®
transponder is in
®
-
---
---
---
see 028
Press reset button on the
transponder board, or disconnect
transponders supply voltage. If
nd
measure.
error occurs again replace
transponder.
If error occurs again replace
transponder
Match customer data
programming.
Change detector. Activate
>Detector change< function in
panel.
If this change is not desired,
connect service PC and run a
configuration check. Re-program
customer data.
---
---
Notify Customer Service.
---
---
---
---
see 028
FB 798951.GB0 / 01.09