Fire Alarm Control Panel IQ8Control C/M
9.3
Display of the analogue values
For service and maintenance work, the current analogue values for all micro modules and components of the
device module can be displayed to check the FACP. The following tables show the individual micro modules,
each with the valid range of analogue values. A fault is detected if the current measured value is outside the
valid value range during checking.
Analogue value is too large: Short circuit/the current flow is too high in this component
Analogue value is too small: Interruption/contact problem in this component
Switching on the display
Test
Press key
"IO no." IQ8 Control:
selected module (I/O no.)
1 Ana 1
2 Ana 1
3 Ana 1
* with basic module
1 SAS relay
2 Serial interface
3 Micro module
Fig. 99: Diagnostics display
Switching off the display
F1
Press key
112
Test
1 = basic module
2 = extension module plug 1
2 = extension module plug 2
Ana 2
Ana 3
Ana 2
Ana 3
Ana 2
Ana 3
*with device module
1 3 relay
2 Transmission device
3 Primary loop
F4
or
F3
"IO No."
Ana 4
Ana 5
Ana 4
Ana 5
Ana 4
Ana 5
*with extension module
1 Micro module slot 1
2 Micro module slot 2
3 Micro module slot 3
FB 798951.GB0 / 01.09