4.1.4 Specification Power supply module (Part No. 802426)

Main voltage
Rated current
Rated frequency range
Rated frequency
Output voltage
Current for ext. devices
Permissible current consumption with
2 x 24 Ah batteries and 72 hour
emergency power supply
Battery capacity
Battery charge voltage
Undervoltage protection
Ambient temperature
Storage temperature
Ambient conditions
Protection class
Compatibility
FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
: 230 V AC (+10% / -15%),
: 0,7 A
: 50 to 60 Hz (ref. to nameplate)
: 50 Hz
: 12 V DC
: max. 2A
:
max. 650 mA
:
max. 2 x 12 V DC / 24 Ah (= 48 Ah)
:
13,65 V DC @ 25 °C
:
≤ 9,5 V DC (with jumper BR2 switch-on / off)
: -5 °C to +45°C
: -5 °C to +50°C
: class 3k5 according to DIN EN 60721-3-3
: I according to DIN EN 6050
: Part No. 802426 Index G or higher
The power supply module is suited for the Fire Alarm Control
Panels IQ8Control C/M with the required Basic module (Part No.
772481/-82).
The required loop voltage (27,5 V or 42 V for esserbus
must be selected on the power supply module with jumper BR4!
For IQ8Control C/M fire alarm control panels it is possible to use
the power supply module from hardware version Index G as a
replacement module. Pay attention to the settings on the power
supply module of FACP IQ8Control C/M and the Index of the
hardware that is used!
Damage to the system!
Before connecting the alternating voltage (230V AC) read the
panel's identification plate. It is not permitted to connect a voltage
other than that shown on the identification plate (sticker in the
panel housing).
®